Requests Details

Request No.2017/2
PriorityStandard
Date Reported17th Jan 2017
Reported Byevav
AreaCARM2
Managed Bycatherinem
DescriptionAE Smith reported that air pressure is too high in CARM 2. Could you please have a look! Update: Hi Ru, Just an interim report on works that were done today. Checked issue with Carm 2 over pressure. Check that all VSD’s were in auto. Found Booster Fan 2 running to the incorrect settings. Adjusted VDS setting. VSD now OK. Checked operation of both systems spill and outside air dampers. All OK Found that there is no air coming out of the spill air grills when the dampers were open. Inspected return air fire dampers. All OK Contacted Mark from AE Smith, Arranged for both of us to be onsite on Friday morning to find the cause of the problem. Also inspected some oil drops within Calm 2 Found oil is coming from the top of the duct, there is no mechanical equipment above the ductwork. Unsure where the oil is coming from. Did notice that the oil is a rather thick type. Regards, Paul Barnes
Service ProviderCortrols
Invoice Number
Date Notified17th Jan 2017
Date Resolved01st Nov 2018

Note Details

No Note attached