Request No. | 2017/2 |
---|---|
Priority | Standard |
Date Reported | 17th Jan 2017 |
Reported By | evav |
Area | CARM2 |
Managed By | catherinem |
Description | AE Smith reported that air pressure is too high in CARM 2. Could you please have a look! Update: Hi Ru, Just an interim report on works that were done today. Checked issue with Carm 2 over pressure. Check that all VSD’s were in auto. Found Booster Fan 2 running to the incorrect settings. Adjusted VDS setting. VSD now OK. Checked operation of both systems spill and outside air dampers. All OK Found that there is no air coming out of the spill air grills when the dampers were open. Inspected return air fire dampers. All OK Contacted Mark from AE Smith, Arranged for both of us to be onsite on Friday morning to find the cause of the problem. Also inspected some oil drops within Calm 2 Found oil is coming from the top of the duct, there is no mechanical equipment above the ductwork. Unsure where the oil is coming from. Did notice that the oil is a rather thick type. Regards, Paul Barnes |
Service Provider | Cortrols |
Invoice Number | |
Date Notified | 17th Jan 2017 |
Date Resolved | 01st Nov 2018 |